All ductwork and
equipment shall be supported using wire rope cable terminated by Cable Locks.
All Cable Locks shall have an Ultimate Breaking Strength (U.B.S.) of at least 5
times the wire rope published Working Load Limit (W.L.L.). All wire rope shall
have a U.B.S. of 5 times the published W.L.L. Wire ropes shall be of the size
and spaced per manufacturers printed specifications.
Wire Rope and Cable Locks shall be as supplied by Duro Dyne Corporation.
| Description | Construction | Working
Load Limit WLL |
Minimum
Ultimate Breaking Strength (U.B.S.) |
| CL
23 Cable Lock |
Stainless
Steel Sintered Steel Zinc Alloy |
250* | 1250* With 1/8" Wire Rope |
| 640* | 3200* With 3/16" Wire Rope | ||
| Description | Construction | Working
Load Limit WLL |
Minimum
Ultimate Breaking Strength (U.B.S.) |
| CL
18 Cable Lock |
Stainless
Steel Sintered Steel Zinc Alloy |
150* | 750* With 3/32" Wire Rope |
| 225* | 1125* With 1/8" Wire Rope | ||
| Description | Construction | Working
Load Limit WLL |
Minimum
Ultimate Breaking Strength (U.B.S.) |
| CL
12 Cable Lock |
Stainless
Steel Sintered Steel Zinc Alloy |
75* | 375* With 1/16" Wire Rope |
| 150* | 750* With 3/32" Wire Rope | ||
WIRE ROPE SPECIFICATION
CARBON STEEL, GALVANIZED
Galvanized steel wire rope, supplied by Duro Dyne is manufactured to exacting standards and statistically tested to verify the breaking strength. Duro Dyne recommends only using wire rope supplied by Duro Dyne. The chart below outlines the specifications.
| Wire Rope Size | Tolerance | Rope Construction |
| 1/8 | +.014 / -.007 | 7 x 7 |
| 3/16 | +.018 / -.009 | 7 x 19 |
| 1/16 | +.010 / -.006 | 7 x 7 |
| 3/32 | +.012 / -.006 | 7 x 7 |
IMPORTANT:
Dyna-Tite Cable
Lock and wire rope each have working load limits which may not be equal. Always
use the lower of the two working load limits.
Wire rope is not included with Dyna-Tite Cable Lock.
|
APPLICABLE SMACNA STANDARD |
SPECIFICATION DATA |
|
The selection of a hanging system should not be taken lightly not only because it involves a significant portion of the erection labor, but also because an inadequate hanging system can be disastrous. In any multiple hanging system, the failure of one hanger transfers the load to adjacent hangers. If one of these fail, an even greater load is transferred to the next. The result is a cascading failure in which an entire run of duct might fail. There are many hanger alternatives, especially in the upper attachments. Besides structural adequacy, the contractor's choice of hanging system must also take into account the particulars of the building structure, the skills of the workmen, the availability of tooling and the recommendations of the fastener manufacturer. Because of these variables, it is suggested that the hanging system be the contractor's choice, subject to the approval of the mechanical engineer. |
|
CL23 RECTANGULAR DUCT
HANGING TABLE
| Maximum
Half of Duct Perimeter |
10
ft Spacing 1 Pair |
8
ft Spacing 1 Pair |
5
ft Spacing 1 Pair |
4
ft Spacing 1 Pair |
| p/2 = 30" | 1/8 | 1/8 | 1/8 | 1/8 |
| p/2 = 72" | 1/8 | 1/8 | 1/8 | 1/8 |
| p/2 = 96" | 3/16 | 1/8 | 1/8 | 1/8 |
| p/2 = 120" | 3/16 | 3/16 | 1/8 | 1/8 |
| p/2 = 168" | 3/16 | 3/16 | 3/16 | 3/16 |
| p/2 = 192" | 3/16 | 3/16 | 3/16 | 3/16 |
| Maximum
Round Pipe Diameter |
10
ft Spacing Single Wire |
8
ft Spacing Single Wire |
5
ft Spacing Single Wire |
4
ft Spacing Single Wire |
| 10" | 1/8 | 1/8 | 1/8 | 1/8 |
| 18" | 1/8 | 1/8 | 1/8 | 1/8 |
| 24" | 1/8 | 1/8 | 1/8 | 1/8 |
| 36" | 1/8 | 1/8 | 1/8 | 1/8 |
| 50" | 3/16 | 3/16 | 1/8 | 1/8 |
| 60" | 3/16 | 3/16 | 3/16 | 1/8 |
| 84" | 3/16 | 3/16 | 3/16 | 3/16 |
CL18 RECTANGULAR DUCT
HANGING TABLE
| Maximum
Half of Duct Perimeter |
10
ft Spacing 1 Pair |
8
ft Spacing 1 Pair |
5
ft Spacing 1 Pair |
4
ft Spacing 1 Pair |
| p/2 = 30" | 3/32 | 3/32 | 3/32 | 3/32 |
| p/2 = 72" | 1/8 | 1/8 | 1/8 | 3/32 |
| p/2 = 96" | 1/8 | 1/8 | 1/8 | |
| p/2 = 120" | 1/8 | 1/8 | ||
| Maximum
Round Pipe Diameter |
10
ft Spacing Single Wire |
8
ft Spacing Single Wire |
5
ft Spacing Single Wire |
4
ft Spacing Single Wire |
| 10" | 3/32 | 3/32 | 3/32 | 3/32 |
| 18" | 1/8 | 1/8 | 3/32 | 3/32 |
| 24" | 1/8 | 1/8 | 1/8 | 3/32 |
| 36" | 1/8 | 1/8 | 1/8 | 1/8 |
| 50" | 1/8 | 1/8 | ||
| 60" | 1/8 | |||
CL12 RECTANGULAR DUCT
HANGING TABLE
| Maximum
Half of Duct Perimeter |
10
ft Spacing 1 Pair |
8
ft Spacing 1 Pair |
5
ft Spacing 1 Pair |
4
ft Spacing 1 Pair |
| p/2 = 30" | 1/16 | 1/16 | 1/16 | 1/16 |
| p/2 = 72" | 3/32 | 3/32 | 1/16 | |
| p/2 = 96" | 3/32 | 3/32 | ||
| p/2 = 120" | 3/32 | 3/32 | ||
| Maximum
Round Pipe Diameter |
10
ft Spacing Single Wire |
8
ft Spacing Single Wire |
5
ft Spacing Single Wire |
4
ft Spacing Single Wire |
| 10" | 1/16 | 1/16 | 1/16 | 1/16 |
| 18" | 3/32 | 3/32 | 1/16 | 1/16 |
| 24" | 3/32 | 3/32 | 1/16 | |
| 36" | 3/32 | 3/32 | ||
| 50" | 3/32 | |||
NOTES:
Tables are
calculated using a normal duct construction and reinforcement
weight as outlined in SMACNA Duct Construction Standards.
For special applications refer to specification table of working load limits.